Ht-instruments MACROTEST G3 Manuel d'utilisateur Page 75

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 108
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 74
MACROTESTG3 - COMBIG3
EN - 74
10
Press the GO/STOP key on the instrument to measure
the Z2 impedance and complete the V% voltage drop
measurement. During this whole stage, do not
disconnect the measuring leads of the instrument from
the system being tested
In case of positive result (maximum percentage value
of calculated voltage drop according to § 12.11 <
set limit value), the screen to the side is displayed by
the instrument, which contains the value of the Z2 end
of line impedance together the Z1 (Offset) value.
Press the SAVE button or touch the icon to save
the measurement (see § 7.1)
11
In case of negative result (maximum percentage
value of calculated voltage drop according to §
12.11 > set limit value), the screen to the side is
displayed by the instrument, which contains the value
of the Z2 end of line impedance together with the Z1
(Offset) value. Press the SAVE button or touch the
icon to save measurement (see § 7.1)