4. Press GO/STOP to start the test. In case no error
conditions occur, the instrument displays the message
Measuring…” as shown in the screen to the side.
15/05/12 15:34:26
Ins. Test : 1000 V
Ri min : 1.0 M
Mode : Timer
Vtest 1020 V
Ri(+)min - - -
M
Test time: 10s
Measuring…
Selection
M
5. When measurement is complete, the instrument provides
the Ri(+)min value, i.e. the minimum value of insulation
resistance of the PV module/string (or of other metal
masses) being tested, continuously measured during the
whole duration of measurement. If the result is higher
than the minimum limit set, the instrument displays the
message “Outcome:OK”; otherwise, it displays the
message “Outcome:NO” as shown in the screen to the
side.
6. Press the SAVE key to store the test result in the
instrument’s memory (see § 7.2) or the ESC/MENU key
to exit the screen without saving and go back to the main
measuring screen.
15/05/12 15:34:26
Ins. Test : 1000 V
Ri min : 1.0 M
Mode : Timer
Vtest = 1020 V
Ri(+)min = >200
M
Test time: 200s
Outcome: OK