6.5.3.1. Anomalous situations
1. In case the instrument detects a voltage higher than 5V at
its terminals E and C, it does not carry out the test, gives
out a long sound and displays the message “Voltage >
Lim”.
15/05/12 15:34:26
RPE max : 1
Rcal : - - -
Rpe = - - -
Itest = - - - mA
Voltage > Lim
Selection
LOW
2. In case the instrument detects that the calibrated
resistance is higher that the measured resistance, the
instrument gives out a long sound and displays the
message: “Calibration not OK”
15/05/12 15:34:26
RPE max : 1
Rcal : - - -
Rpe = - - -
Itest = - - - mA
Calibration not OK
Selection
LOW
3. In case the instrument detects a resistance higher than
5 at its terminals, it gives out a long sound, zeroes the
compensated value and displays the message
“Calibration reset”.
15/05/12 15:34:26
RPE max : 1
Rcal : 0.00
Rpe = - - -
Itest = - - - mA
Calibration reset
Selection
LOW